یو پی اس MASTERYS IP+ RAIL OLI

یو پی اس MASTERYS IP+ RAIL OLI

Overhead Line Infrastructure UPS

Key Benefits

  • Full Range 20-120 kVA
  • IP Protection Degree: IP31 standard
  • High Efficiency
  • Coated Electronic Boards
  • Full Galvanic Isolation
  • External Manual Bypass
  • (Low Smoke Zero Halogen option)
  • Socomec’s IP+ Rail (OLI) offers increased energy availability: the system can take inputs from both a 25 kV overhead line as well as a 400V AC mains supply.

    As a result, this solution potentially avoids the need for a diesel generator and its associated maintenance, fuel storage and refuelling costs.

    The innovative rectifier stage converts the input voltage into a DC voltage that will charge both the UPS battery and supply the input stage of the inverter.

    In normal mode*, the upstream voltage of the rectifier corresponds to the transformed single phase voltage of the overhead line. The transformer and voltage stabiliser eliminates voltage sags and surges related to current draw of locomotives. When this voltage is not present or is no longer with intolerance, it is the 3 phase DNO supply which is sent directly to the UPS rectifier.

    The inverter converts the DC voltage, provided either from the rectifier output or from the battery in a perfect sinusoidal voltage distributed to the critical loads. The UPS is also equipped with an automatic bypass which allows a no-break transfer of the load directly onto the mains supply in case of overload or faults.

    An external manual bypass completes the solution to allow for maintenance of the UPS.

ویژگی های اختیاری و استاندارد

Standard electrical features

  • Dual input mains.
  • Internal maintanance bypass.
  • Backfeed protection: detection circuit.
  • EBS (Expert Battery System) for battery management.

Electrical options

  • Long-life batteries.
  • External battery cabinet (degree of protection up to IP32).
  • External temperature sensor.
  • Additional battery chargers.
  • Additional transformer.
  • Parallel kit.
  • Cold start.
  • ACS synchronization system.
  • Neutral creation kit for mains without neutral.
  • Tropicalization and anti-corrosion protection for electrical boards.
Standard communication features
  • Multilanguage graphic display.
  • Dry-contact interface.
  • MODBUS/JBUS RTU.
  • Embedded LAN interface (web pages, email).
  • 2 slots for communication options.

Communication options

  • Remote mimic panel.
  • Profibus.
  • MODBUS TCP.
  • NET VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.

Remote maintenance

LINK-UPS: maintenance software for continuous 24/7 monitoring of the SOCOMEC UPS.

داده های تکنیکی
Sn [kVA] 10 15 20 30 40 60 80
Pn [kW] - 3/1 9 13,5 18 27 32 48  
Pn [kW] - 3/3 9 13,5 18 27 32 48 64
Parallel configuration(1) Available up to 6 units for power extension or redundancy
Efficiency Up to 95% in VFI –SS-11 mode TÜV verified (transformer excluded)
Input
Rated voltage 400 V (3ph + N)
Voltage tolerance ± 20%(3) (up to -40% @ 50% of rated power)
Rated frequency 50/60 Hz
Frequency tolerance ± 10%
Power factor / THDI(2) 0.99 / < 3%
Output
Rated voltage 1ph+n/2ph 230(220/240 configurable)(3)
3ph + N: 400 V (380/415 V configurable) (3)
Voltage tolerance ± 1%
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable from 1% to 8% with generator set)
Total output voltage distortion - linear load < 1 % 
Total output voltage distortion - non-linear load < 5 %
Overload 125% for 10 minutes, 150% for 1 minute 
Crest factor 3:1 (complying with IEC 62040-3)
Power factor without derating From 0.6 lagging up to 0.9 leading
Bypass
Rated voltage 1ph + N: 230 V, 3ph + N: 400 V
Voltage tolerance ± 15% (configurable from 10% to 20% with generator set)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable from 1% to 8% with generator set)
Environment
Operating ambient temperature from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0 % - 95 % without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m
(ISO 3746)
< 52 dBA < 55 dBA < 65 dBA
Dimension and weight - UPS single cabinet  
Dimensions (3/1) W x D x H 600 x 800 x 1400 mm 1000 x 835 x
1400 mm
-
Dimensions (3/3) W x D x H 600 x 800 x 1400 mm 1000 x 835 x
1400 mm
Weight (3/1) 230 kg 250 kg 270 kg 330 kg 490 kg 540 kg  -
Weight (3/3) 230 kg 250 kg 270 kg 320 kg 370 kg 500 kg 550 kg
Degree of protection IP31 and IP52 as option (according to IEC 60529) Coated electronic boards(4)
Colours RAL 7012 
Standards
Safety EN 62040-1 (TÜV SÜD certified), EN 60950-1, LU 1-085 (Section 12 LU) (4)
Type and performance EN 62040-3 [VFI-SS-111]
EMC EN 62040-2 (2nd Edition) G-222 EN 50121
Product declaration CE

(1) With transformer on input/bypass side.

(2) For source THDV < 2 % and nominal load.

(3) Three-phase 220-230-240 V from 15 to 40 kVA .