یو پی اس MASTERYS GP from 10 to 120 kVA/kW
        
            
        
     
    
    
    
    
        
        
          ویژگی های اختیاری و استاندارد
        
        
            Standard electrical features
Dual input mains.
Internal maintanance bypass.
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery management.
Electrical options
    - External battery cabinet.
- External temperature sensor.
- Additional battery chargers.
- Galvanic isolation transformer.
- Parallel kit.
- ACS synchronization system.
Standard communication features  
MODBUS/JBUS RTU.
2 slots for communication options.
Communication options
    - Dry-contact interface.
- Remote mimic panel.
- MODBUS TCP.
- PROFIBUS
- NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems.
Remote monitoring service
    
    
    
 
     
    
        
        
            داده های تکنیکی 
        
        
             
 
    
        
            | 
                
                    
                        | Sn [kVA] | 15 | 20 |  
                        | Pn [kW] | 13.5 | 18 |  
                        | Input / output 3/1 | • | • |  
                        | Parallel configuration | 1+1 (1) |  
                
                    
                        | Input |  
                        | Rated voltage | 400 V (3ph + N) |  
                        | Voltage tolerances | 240 V to 480 V(2) |  
                        | Rated frequency | 50/60 Hz ± 10% |  
                        | Power factor / THDI | 0.99 / < 3% |  
                
                    
                        | Output |  
                        | Rated voltage | 1ph + N: 230 V (can be configured 220/240 V) |  
                        | Voltage tolerance | static load ±1% dynamic load in accordance with VFI-SS-111 |  
                        | Rated frequency | 50/60 Hz |  
                        | Frequency tolerance | ± 2% (configurable from 1% to 8%) |  
                        | Overload | 125% for 10 minutes, 150% for 1 minute |  
                        | Crest factor | 3:1 |  
                
                    
                        | Bypass |  
                        | Rated voltage | rated output voltage |  
                        | Voltage tolerance | ± 15% (configurable with from 10% to 20%) |  
                        | Rated frequency | 50/60 Hz |  
                        | Frequency tolerance | ± 2% (configurable for Genset compatibility) |  
                
                    
                        | Efficiency |  
                        | Online mode @ 100 % of load | up to 94% |  
                
                    
                        | Environment |  
                        | Operating ambient temperature | from 0 °C up to 40(2) °C (from 15 °C to 25 °C for maximum battery life) |  
                        | Relative humidity | 0% - 95% without condensation |  
                        | Maximum altitude | 1000 m without derating (max. 3000 m) |  
                        | Acoustic level at 1 m (ISO 3746)
 | < 52 dBA | < 55 dBA |  
                
                    
                        | UPS cabinet |  
                        | Dimensions W x D x H | 444 x 795 x 800  / 1000 / 1400 mm |  
                        | Weight | 105 kg(3) | 110 kg(3) |  
                        | Degree of protection | IP20 |  
                        | Colours | RAL 7012 |  
                
                    
                        | Standards |  
                        | Safety | EN 62040-1 (TÜV SÜD certified), EN 60950-1 |  
                        | Performance | EN62040-3 (VFI-SS-111) |  
                        | EMC | EN62040-2 |  
                        | Product declaration | CE |  | 
    
(1) The standard model is prepared for a 1+1 redundant system. Upon request, it is possible to have connected up to 6 modules in a parallel system.
(2) Conditions apply.
(3) Without batteries.